ADDITIONAL INFORMATION:
In-line turbine meter with die cast aluminum body and polypropylene turbine has a flow range of 2-32 GPM with an accuracy of +/- 1% and +/- 0.2% repeatability. This meter is UL approved for use with Gasoline, Diesel Fuel and Kerosene and features a high contrast LCD display with a resettable 5 digit batch total and a 6 digit non-resettable cumulative total. Pressure loss is less than 0.4 PSI at 30 GPM. LCD display is rotatable to allow maximum connection flexibility, 1” NPTM x 1”NPTF connections